Overvoltages on Power Filters under Energizing Industrial Power System Transformer

The practice of operating industrial power supply systems containing filter circuits has shown that filter tuning can have a significant impact on filter performance. On the basis of simulations of a real power supply system carried out by the Matlab / Simulink package, the results of a study of the...

Full description

Saved in:
Bibliographic Details
Main Author: Yuriy Varetsky
Format: Article
Language:English
Published: Lviv Polytechnic National University 2020-12-01
Series:Energy Engineering and Control Systems
Subjects:
Online Access:https://science.lpnu.ua/jeecs/all-volumes-and-issues/volume-6-number-2-2020/overvoltages-power-filters-under-energizing
Tags: Add Tag
No Tags, Be the first to tag this record!
Description
Summary:The practice of operating industrial power supply systems containing filter circuits has shown that filter tuning can have a significant impact on filter performance. On the basis of simulations of a real power supply system carried out by the Matlab / Simulink package, the results of a study of the impact of filter manufacturing tolerances on the filter transients under transformer energizing are presented. The most severe transients are observed for filter circuits in the power supply systems of electric arc furnaces due to frequently repeated operating energizing furnace transformers. This article summarizes the analysis of overvoltages on capacitors and reactors for various configurations of the filter circuit, arising during energizing the arc furnace transformer, taking into account the possible detuning of the filters.
ISSN:2411-8028
2415-7287