Research on Trend Analysis and Early Warning Technology of Smart Substation Telemetry Data Based on ARIMA-BP Combined Model

In order to perform fault early warning on the secondary protection devices of smart substations based on monitoring data, a trend analysis and early warning method of smart substation telemetry data based on the ARIMA-BP combined model is proposed.Based on the analysis of the relay protection fa...

Full description

Saved in:
Bibliographic Details
Main Authors: ZHOU Ke, WANG Xiaoming, LI Xiaobo, SONG Yi
Format: Article
Language:Chinese
Published: Harbin University of Science and Technology Publications 2023-02-01
Series:Journal of Harbin University of Science and Technology
Subjects:
Online Access:https://hlgxb.hrbust.edu.cn/#/digest?ArticleID=2182
Tags: Add Tag
No Tags, Be the first to tag this record!
Description
Summary:In order to perform fault early warning on the secondary protection devices of smart substations based on monitoring data, a trend analysis and early warning method of smart substation telemetry data based on the ARIMA-BP combined model is proposed.Based on the analysis of the relay protection failure of the intelligent substation, the remote measurement data source for the early warning of the device status trend is selected, and the ARIMA-BP combined forecasting model is established based on the analysis of the characteristics of the data source.Based on the ARIMA-BP combined forecasting model and the historical telemetry data of the equipment, the equipment operation trend prediction is carried out.Taking the remote measurement data of the line protection device in a 220kV substation as an example, the prediction error rate of the ARIMA-BP combined model is 5% and 9% lower than that of the ARIMA model and the BP model alone. The superiority of ARIMA-BP combined model in telemetry trend prediction and early warning is verified.
ISSN:1007-2683